Project Summary


For the UK Meat and Food Development Facility, our team supported a robust HVAC equipment package built to handle process-adjacent ventilation demands and tight space control. The solution combined:

  • a large Daikin Rebel Applied rooftop sized for high airflow and multi-zone control.

  • a 25‑ton 100% outside-air rooftop with hot gas reheat and leak detection.

  • a 15‑ton rooftop with power exhaust and economizer controls.

  • multiple AHRI-certified hot water “booster” coils for distributed heating/reheat needs.


What We Delivered (Highlights)

1) High-Capacity Rooftop — Daikin Rebel Applied (52 Tons)

  • Daikin Rebel Applied, 52‑ton, high efficiency packaged DX system.

  • Airflow / Scale: Designed for 10,400 CFM, with a large cabinet platform suited for high-volume applications.

  • Refrigerant: R‑32.

  • Controls / Integration: MicroTech IV controls with BACnet MS/TP integration; pressure controls include a building pressure sensor.

  • Ventilation Strategy: 0–100% economizer with comparative enthalpy control and barometric relief; includes exhaust/return fan configuration and airflow measurement across supply/return/exhaust.

  • Construction & Durability: Thermally broken double-wall construction and stainless drain pan; high SCCR and corrosion-resistance testing details.


2) Dedicated Outdoor Air / Process Ventilation Support — 100% OA, Hot Gas Reheat

  • Daikin Package System, 25‑ton configured with 100% outside air and no return opening.

  • Humidity/Temperature Control: Includes modulating hot gas reheat (MHGRH) for discharge-air stability.

  • Refrigerant + Safety: R‑32 refrigerant plus refrigerant leak detection and a condenser vandal guard.

  • Controls / BAS: MicroTech controls with BACnet MS/TP; single-zone VAV application.

  • Filtration: MERV 13 filtration in a 2" only rack.

  • Electrical / Serviceability: Single disconnect, factory powered GFI, phase voltage monitor.


3) Rooftop with Economizer + Power Exhaust — 15 Tons

  • Daikin Package System, 15‑ton with 0–100% economizer using comparative enthalpy control and an airfoil power exhaust fan.

  • Refrigerant: R‑32.

  • Controls / BAS: MicroTech controls and BACnet MS/TP integration; includes a building pressure sensor.

  • Filtration: MERV 13 filtration in a 2" only rack.


Hydronic Heating / Reheat Components (Booster Coils)

To support distributed heating and temperature control points, the package also included multiple Daikin Applied hot water “booster” coils , AHRI-certified and documented with performance and dimensional data

Get in Touch

Lexington Office

680 Bizzell Dr. 

Lexington, KY 40510

859.255.9665

​

Louisville Office

13151 Middletown Industrial Blvd

Louisville, KY 40223

502.473.0829

​

Paducah Office

115 Eaglet Cove

Paducah, KY 42003

​270.898.6976

  • Facebook
  • LinkedIn
  • Instagram

Thanks for submitting!

bottom of page