HTx104-PE

Probe and Sensor Node Configurations (max.)
1 probes x 4 sensor nodes/probe
2 probes x 2 sensor nodes/probe
Installed Airflow Accuracy
? 2 sq.ft. [0.185 sq.m.]: �3% of reading
> 2 sq.ft. [0.185 sq.m.]: �(3% to 10%), typical (increases with
increasing duct size). May be improved by field adjustment using the
Field Adjust Wizard (FAW) to a reliable reference.
PE Sensor Density: Refer to the PE sensor density table.
Sensor Node Averaging Method
Airflow: Independent, arithmetic average
Temperature: Independent, velocity weighted average
Listings and Compliance
UL: UL-873 and CSA C22.2 No. 24
CE: Non-UK European shipments only
UKCA: UK shipments only
BACnet International: BTL Listed (HTN104 transmitter)
FCC: This device complies with Part 15 of the FCC rules
RoHS: This device is RoHS2 compliant
Environmental Limits
Temperature:
Probes: -20 to 160 ?F [-28.9 to 71.1 ?C]
Transmitter: -20 to 120 ?F [-28.9 to 48.9 C]
Humidity: (non-condensing)
Probes: 0 to 100%
Transmitter: 5 to 95%