Comprehensive Evaluation of HVAC System Upgrade or Replacement Needs: A Multi-Dimensional Assessment for Kentucky Businesses

  • Writer: Corey Mullikin
    Corey Mullikin
  • Nov 14, 2025
  • 12 min read

HVAC System Evaluation for Improvement or Replacement


Introduction


Heating, ventilation, and air conditioning (HVAC) systems are the backbone of indoor environmental quality, energy efficiency, and occupant comfort in commercial buildings. As these systems age or as operational requirements evolve, facility managers and business owners must periodically assess whether their HVAC infrastructure remains fit for purpose or if upgrades—or even full replacement—are warranted.


This report provides a comprehensive, actionable framework for evaluating your company’s HVAC system across six critical dimensions: Indoor Air Quality (IAQ), Energy Consumption, Noise Pollution, Code Compliance, Maintenance Costs, and Tax Saving Opportunities. Each section details key performance indicators (KPIs), industry benchmarks, signs of inefficiency or non-compliance, and practical guidance for on-site evaluation and data collection.


Special attention is given to Kentucky-specific codes, incentives, and rebate programs, ensuring that recommendations are both locally relevant and aligned with current best practices.


Indoor Air Quality (IAQ)


Key Performance Indicators and Benchmarks


Indoor Air Quality is a primary determinant of occupant health, productivity, and satisfaction. HVAC systems play a central role in controlling IAQ by managing ventilation, filtration, humidity, and contaminant removal. The following table summarizes the most critical IAQ parameters, their recommended benchmarks, and typical measurement methods for commercial environments:

Parameter

Benchmark/Standard

Measurement Method

Notes

Carbon Dioxide (CO₂)

< 800–1000 ppm (ASHRAE, CDC)

Direct-read IAQ monitor

Indicator of ventilation adequacy; >1000 ppm signals poor ventilation

Temperature

68–76°F (20–24.4°C)

Thermometer/IAQ monitor

OSHA/ASHRAE comfort range

Relative Humidity (RH)

30–50% (EPA, ASHRAE)

Hygrometer/IAQ monitor

>60% promotes mold; <30% causes dryness

Carbon Monoxide (CO)

< 9 ppm (EPA 8-hr avg)

Direct-read IAQ monitor

Should be near outdoor levels; >9 ppm is hazardous

Particulate Matter (PM2.5)

< 12 μg/m³ (EPA annual avg)

Laser particle counter

High levels linked to respiratory issues

Total Volatile Organic Compounds (TVOC)

< 500 μg/m³ (WELL/RESET)

PID sensor/IAQ monitor

High TVOC signals off-gassing, chemical use

Airborne Biologicals

No visible mold; minimal allergens

Visual, swab, or air sampling

Mold, bacteria, and allergens must be controlled

Table 1: IAQ Performance Benchmarks for Commercial HVAC Systems


These benchmarks are drawn from ASHRAE, EPA, WELL, and RESET standards, and reflect both regulatory requirements and best practices for occupant health and comfort.


Signs of IAQ Inefficiency and Common HVAC-Related Sources


Several symptoms and system conditions indicate that your HVAC system may be contributing to poor IAQ:


  • Elevated CO₂ Levels: Persistent readings above 1000 ppm suggest insufficient outdoor air supply or poor air distribution, often due to blocked dampers, malfunctioning economizers, or inadequate system sizing.

  • Temperature and Humidity Fluctuations: Inconsistent or uncomfortable conditions may result from improper control calibration, oversized/undersized equipment, or failing sensors.

  • High PM2.5 or Visible Dust: Indicates inadequate filtration, dirty ducts, or infiltration from outdoors or construction activities.

  • Musty Odors or Visible Mold: Suggests moisture problems, condensate drain issues, or poor humidity control, often exacerbated by dirty coils or clogged drain pans.

  • Frequent Occupant Complaints: Reports of headaches, respiratory symptoms, or fatigue may be linked to VOCs, biologicals, or poor ventilation.


Common HVAC-related sources of IAQ problems include:

  • Dirty or undersized filters (low MERV rating)

  • Poorly maintained coils and drain pans (mold/bacteria growth)

  • Leaky or unbalanced ductwork (cross-contamination)

  • Inadequate outdoor air intake or blocked vents

  • Use of low-quality or deteriorating insulation materials


On-Site IAQ Measurement Tools and Sampling Methods


A robust IAQ assessment combines direct measurement, visual inspection, and occupant feedback. Recommended tools and methods include:

  • Direct-Read IAQ Monitors: Devices like the TSI Q-Trak 7575 provide real-time readings of CO₂, CO, temperature, and humidity.

  • Particulate Counters: Instruments such as the TSI DustTrak or AeroTrak measure PM2.5 and PM10 concentrations, critical for assessing filtration and dust control.

  • Photoionization Detectors (PID): Used for TVOC measurement, identifying chemical off-gassing or cleaning product residues.

  • Moisture Meters: Detect hidden water intrusion in walls, ceilings, or insulation, which can foster mold growth.

  • Visual Inspection: Check for visible mold, water stains, dirty filters, and blocked vents.

  • Occupant Surveys: Gather feedback on comfort, odors, and symptoms to identify problem areas.


Sampling Protocols:

  • Take measurements at breathing zone height (2.5–5 feet above floor), away from direct air streams, doors, or windows.

  • Compare indoor readings to outdoor baselines for CO₂, CO, PM, and TVOC.

  • Sample during normal operating hours and at peak occupancy for representative data.


Data Collection Guidance for Facility Managers


To facilitate a thorough IAQ assessment, collect and document the following:

  • Building age, size, occupancy, and function

  • HVAC system type, age, and maintenance history

  • Filter type and replacement schedule (MERV rating)

  • Outdoor air intake locations and damper positions

  • Recent renovations, water damage, or pest control activities

  • IAQ monitoring data (CO₂, PM2.5, TVOC, RH, temperature)

  • Occupant complaints and health symptoms


Actionable Steps:

  1. Schedule a baseline IAQ survey using calibrated instruments.

  2. Record all readings and observations in a standardized data collection form.

  3. Identify and prioritize areas with readings outside recommended benchmarks.

  4. Implement corrective actions (e.g., filter upgrades, coil cleaning, increased ventilation) and re-test to confirm improvements.


Energy Consumption


HVAC Efficiency KPIs and Industry Benchmarks


Energy consumption is a major driver of operating costs and environmental impact for commercial buildings. HVAC systems typically account for 40–60% of total building energy use. The following KPIs and benchmarks are essential for evaluating HVAC energy performance:

Metric

Benchmark/Standard (2023+)

Notes

SEER2 (Cooling)

≥ 14.3 (residential, Kentucky)

New DOE standard as of Jan 2023; SEER2 replaces SEER

EER2 (Full-load Cooling)

≥ 11.7 (residential, Kentucky)

EER2 replaces EER; reflects field conditions

HSPF2 (Heating)

≥ 7.5 (residential, Kentucky)

HSPF2 replaces HSPF; for heat pumps

IEER (Commercial)

≥ 14.8 (small commercial, 65–135k Btu/h)

2023 DOE standard for commercial packaged units

COP (Coefficient of Performance)

≥ 3.4 (commercial)

Higher is better; applies to heat pumps, chillers

Energy Use Intensity (EUI)

< 50–80 kBtu/ft²/year (office benchmark)

Lower is better; varies by building type

Table 2: HVAC Energy Efficiency Benchmarks (2023 DOE Standards)


These standards reflect the latest federal requirements and are enforced for new installations and major retrofits.


Signs of Energy Inefficiency in HVAC Systems


Indicators that your HVAC system is consuming excessive energy or operating inefficiently include:

  • High Utility Bills: Energy costs significantly above peer buildings or historical averages, after adjusting for weather and occupancy.

  • Short Cycling: Frequent on/off cycling of compressors or fans, often due to oversized equipment, faulty controls, or airflow restrictions.

  • Inconsistent Temperatures: Hot/cold spots or poor humidity control, indicating poor air distribution or control issues.

  • Excessive Run Times: Equipment running continuously or failing to reach setpoints, often due to dirty coils, low refrigerant, or control faults.

  • Aging or Obsolete Equipment: Systems older than 15–20 years are typically 30–50% less efficient than modern units.

  • Improperly Set Controls: Thermostats, economizers, or scheduling controls not optimized for occupancy or weather.


On-Site Energy Assessment Procedures and Data Collection


A comprehensive energy assessment should follow the ASHRAE Level 1–3 audit framework:

  1. Utility Bill Analysis: Gather 12–36 months of electricity and gas bills. Calculate Energy Use Intensity (EUI) and compare to similar buildings.

  2. Equipment Inventory: Document all HVAC equipment (make, model, age, capacity, efficiency ratings).

  3. Operating Schedules: Review thermostat settings, occupancy schedules, and control sequences.

  4. Spot Measurements: Use power loggers to measure real-time energy use of major equipment (compressors, fans, pumps) over several days or weeks.

  5. System Performance Testing: Measure supply/return air temperatures, static pressures, and refrigerant levels.

  6. Airflow and Balancing Checks: Assess damper positions, duct leakage, and air distribution.

  7. Benchmarking: Compare system performance to DOE, ENERGY STAR, or CEE directories for similar equipment.


Data to Collect:

  • Equipment nameplate data (SEER2, EER2, HSPF2, IEER, COP)

  • Run times and cycling patterns

  • Maintenance and repair logs

  • Control settings and schedules

  • Utility rates and demand charges


Energy Savings Calculators:

  • Use online tools to estimate savings from upgrading to higher SEER2 or IEER equipment, factoring in local electricity rates and available incentives.


Financial Analysis and Payback Calculations


When considering upgrades or replacements, conduct a life-cycle cost analysis (LCCA) that includes:

  • Initial purchase and installation costs

  • Annual energy savings (kWh, therms, $)

  • Maintenance and repair cost differences

  • Equipment lifespan and salvage value

  • Available rebates and tax credits

  • Discount rate (time value of money)


Simple Payback = (Incremental Cost) / (Annual Savings)


Life-Cycle Cost (LCC) = Initial Cost + Present Value of All Future Operating and Maintenance Costs.


Noise Pollution


Noise KPIs, Benchmarks, and Signs of Excessive HVAC Noise

HVAC-related noise can disrupt productivity, reduce occupant satisfaction, and even violate building codes. Key metrics and benchmarks include:

Room Type

Recommended NC/RC Rating

dBA (approx.)

Subjective Impact

Private Office

NC/RC 30

35

Quiet, no speech interference

Conference Room

NC/RC 30

35

Quiet, clear communication

Classroom

NC/RC 25–35

30–40

Suitable for learning

Open Office

NC/RC 35–40

40–45

Moderate background noise

Hospital Patient Room

NC/RC 25–30

35–40

Restful, minimal disturbance

Table 3: HVAC Noise Criteria Benchmarks (ASHRAE, UFC, Engineering Toolbox)

  • NC (Noise Criterion) and RC (Room Criterion) curves are industry standards for rating HVAC noise. NC/RC 25–35 is typically acceptable for offices and classrooms.

  • QAI (Quality Assessment Index): >5 dB indicates marginal sound quality; >10 dB is objectionable (e.g., rumble, hiss, roar).


Signs of Excessive HVAC Noise:

  • Complaints of lost productivity, speech interference, or stress

  • Audible hums, whines, or throbbing sounds

  • Fluctuating noise levels or excessive low-frequency rumble

  • Measured NC/RC ratings above recommended levels

  • Structureborne vibration causing rattles or discomfort


Measurement Tools and Methods

  • Type 1 Integrating Sound Level Meter: With octave band filters, measures Leq (average sound pressure level) at occupant ear height.

  • RC Mark II and NC Curves: Used to diagnose spectral imbalances (e.g., excessive low-frequency noise).

  • Vibration Meters: Assess equipment-induced vibration transmitted through structure.


Measurement Protocol:

  • Measure with HVAC system on and off to isolate system noise.

  • Record at multiple locations and times, especially near diffusers, returns, and equipment rooms.

  • Calibrate instruments before and after use.


On-Site Evaluation Guidance

  • Inspect fan and motor mounts for proper vibration isolation.

  • Check ductwork for turbulence, pressure drops, and loose fittings.

  • Evaluate damper positions and airflow distribution.

  • Listen for audible tones, rattles, or pulsations during operation.


Remediation Options:

  • Install duct attenuators or sound traps

  • Upgrade to quieter fans or variable-speed drives

  • Improve vibration isolation and equipment mounting

  • Balance airflow to minimize turbulence


Code Compliance (Kentucky and Local)


Regulatory Benchmarks and Inspection Indicators


Kentucky enforces both the 2018 Kentucky Building Code and the 2018 Kentucky Residential Code, with specific amendments for HVAC systems. Key compliance requirements include:

  • Permitting and Licensing: All new HVAC installations and major modifications require permits. Only licensed contractors may perform work.

  • Equipment Sizing: Must be based on ACCA Manual S (for equipment) and Manual J (for load calculations), ensuring proper capacity for the building’s needs.

  • Installation Standards: Equipment must be installed per manufacturer instructions and code requirements, including clearances, access, and safety controls.

  • Combustion Air and Venting: Proper provision for combustion air, venting, and condensate disposal is mandatory.

  • Electrical and Refrigerant Safety: Compliance with National Electric Code (NEC) and EPA refrigerant handling rules.

  • Ductwork and Insulation: Ducts must be sealed, insulated, and tested for leakage as required by code.

  • Flood Hazard Protection: Equipment in flood-prone areas must be elevated or protected per code.


Inspection Indicators:

  • Proper permits and inspection records

  • Equipment nameplate data matching design documents

  • Verified airflow, temperature, and pressure measurements

  • Documentation of load calculations and equipment selection

  • Compliance with local amendments (e.g., Lexington, KY may have stricter requirements)


On-Site Compliance Checklist

  • Verify contractor licensing and permit status

  • Review installation against approved plans and code requirements

  • Inspect for required clearances, access, and labeling

  • Test safety controls, shutoffs, and alarms

  • Confirm duct sealing and insulation

  • Document refrigerant type and handling procedures


Non-Compliance Risks:

  • Fines, rework costs, or denial of occupancy permits

  • Increased liability for safety incidents

  • Voided warranties or insurance coverage


Maintenance Costs and Life-Cycle Cost Analysis


Maintenance KPIs and Signs of High Maintenance Burden

Effective maintenance minimizes downtime, extends equipment life, and controls costs. Key maintenance KPIs include:

KPI

Benchmark/Target

Notes

Annual Maintenance Cost

$0.44–$0.61/ft²/year (median)

2024 ASHRAE data for commercial buildings

Mean Time Between Failures (MTBF)

As high as possible (varies by equipment)

Indicates reliability; higher MTBF is better

Mean Time to Repair (MTTR)

As low as possible

Shorter MTTR means faster repairs

Planned Maintenance % (PMP)

≥ 85%

Proportion of maintenance that is planned vs. reactive

Preventive Maintenance Compliance (PMC)

≥ 90%

% of scheduled PM tasks completed on time

Table 4: Maintenance Cost and Reliability Benchmarks


Signs of High Maintenance Burden:

  • Frequent breakdowns or emergency repairs

  • High ratio of reactive to preventive maintenance

  • Excessive downtime or lost productivity

  • Escalating repair costs, especially for aging equipment

  • Difficulty sourcing replacement parts (obsolete models)

  • Increasing complaints of noise, vibration, or comfort issues


On-Site Maintenance Inspection Checklist and Data Collection


A thorough maintenance assessment should include:

  • Review of maintenance logs (frequency, type, and cost of repairs)

  • Inspection of filters, coils, belts, motors, and controls

  • Verification of lubrication, cleaning, and calibration schedules

  • Assessment of spare parts inventory and lead times

  • Evaluation of maintenance staffing and training

  • Documentation of warranty status and service contracts


Sample Maintenance Checklist:

  • Inspect and replace air filters (monthly/quarterly)

  • Clean coils and drain pans (seasonally)

  • Lubricate motors and bearings (annually)

  • Check refrigerant levels and pressures (seasonally)

  • Test safety controls and alarms (annually)

  • Inspect ductwork for leaks and insulation (annually)

  • Verify thermostat and control operation (seasonally)

  • Record all findings and corrective actions


Data to Collect:

  • Maintenance cost per square foot per year

  • Number and type of service calls (planned vs. unplanned)

  • Equipment age and condition

  • MTBF and MTTR statistics (if tracked)

  • Parts and labor cost breakdowns


Life-Cycle Cost Analysis (LCCA) and Decision Framework

When deciding between repair, retrofit, or replacement, use LCCA to compare total costs over the equipment’s expected life:


LCCA Steps:

  1. Gather all relevant costs: initial purchase/repair, installation, energy, maintenance, and disposal.

  2. Determine the analysis period (e.g., 10, 15, or 20 years).

  3. Discount future costs to present value using an appropriate rate.

  4. Sum all costs for each alternative.

  5. Select the option with the lowest total life-cycle cost.


Repair vs. Replace Considerations:

  • Age and condition of existing equipment

  • Frequency and cost of repairs

  • Energy efficiency gap vs. new equipment

  • Availability of parts and support

  • Impact on IAQ, comfort, and code compliance

  • Potential for incentives or rebates


Rule of Thumb: If annual repair costs exceed 50% of the cost of a new system, or if the system is more than 15–20 years old and inefficient, replacement is often justified.


Tax Saving Opportunities and Incentives (Federal, Kentucky, Local)


Federal Incentives


Energy Efficient Home Improvement Credit (Inflation Reduction Act, 2023–2025):

  • Credit Amount: Up to 30% of qualified expenses, capped at $1,200/year for most improvements, and $2,000/year for qualified heat pumps, water heaters, and biomass stoves/boilers.

  • Eligible Improvements: High-efficiency HVAC systems (meeting CEE highest tier), insulation, windows, doors, and home energy audits.

  • Business Use: If the property is used partly for business, the credit is prorated.

  • Claiming: File IRS Form 5695 for the tax year the property is installed.


Key Requirements:

  • Equipment must meet or exceed CEE highest efficiency tier.

  • Must be new equipment, not used.

  • Labor costs are included for HVAC equipment, but not for building envelope improvements.


Kentucky-Specific Incentives


Kentucky Home Energy Rebates Program:

  • Status: As of November 2025, the program is in development and expected to launch in spring 2025.

  • Scope: Will provide rebates for energy efficiency improvements, including HVAC upgrades, insulation, air sealing, and electrical upgrades.

  • Eligibility: Kentucky residents and businesses; must use qualified contractors.

  • Action: Monitor energyrebates.ky.gov for updates and application portal opening.


Utility Rebates (Lexington, KY):

  • LG&E and KU Energy: Offers cash rebates for ENERGY STAR-certified equipment:

    • $300 for central air conditioners

    • $400 for air source or ductless heat pumps

    • $300 for heat pump water heaters

    • $250 for natural gas furnaces

  • Application: Apply through utility account portal or as a guest user.


Local Programs:

  • WeCare Program: Provides weatherization and energy-saving upgrades to income-qualified households at no cost.


How to Maximize Incentives

  • Stacking: Federal tax credits and state/utility rebates can often be combined, but rebates may reduce the eligible expense for the tax credit.

  • Documentation: Retain manufacturer certifications, receipts, and installation records.

  • Timing: Plan upgrades to coincide with program openings and maximize annual credit caps.

  • Qualified Contractors: Use approved contractors to ensure eligibility for rebates and compliance with program requirements.


Decision Framework: Repair, Retrofit, or Full Replacement


Step-by-Step Evaluation Process

  1. Initial Screening:

    • Review system age, condition, and maintenance history.

    • Identify any code compliance or safety issues.

    • Assess IAQ, comfort, and noise complaints.

  2. Data Collection:

    • Gather utility bills, equipment inventory, and maintenance logs.

    • Conduct on-site measurements for IAQ, energy use, and noise.

  3. Benchmarking:

    • Compare system performance to industry standards and peer facilities.

  4. Financial Analysis:

    • Estimate costs and savings for repair, retrofit, and replacement options using LCCA.

    • Factor in available incentives and rebates.

  5. Risk Assessment:

    • Consider reliability, downtime, and business continuity impacts.

    • Evaluate potential for future code changes or refrigerant phaseouts.

  6. Recommendation:

    • Select the option with the best balance of cost, performance, and risk.

    • Develop an implementation plan and schedule.


Data Collection Templates and On-Site Evaluation Guidance


Use standardized forms to ensure consistent data collection:

  • HVAC System Audit Checklist: Covers visual inspection, performance testing, safety checks, and documentation.

  • Energy Audit Data Sheet: Records utility data, equipment specs, and operating schedules.

  • IAQ Assessment Form: Logs measurement data, occupant feedback, and observed issues.

  • Maintenance Log Template: Tracks service dates, repairs, costs, and downtime.


On-Site Evaluation Tips:

  • Schedule audits during typical operating hours for representative data.

  • Involve facility staff and occupants in identifying problem areas.

  • Use calibrated instruments and follow manufacturer protocols.

  • Document all findings with photos and detailed notes.


Summary Table: HVAC System Evaluation Benchmarks

Dimension

Key KPI/Benchmark

Signs of Inefficiency/Non-Compliance

On-Site Data to Collect

IAQ

CO₂ < 800–1000 ppm, RH 30–50%, PM2.5 < 12 μg/m³, TVOC < 500 μg/m³

High CO₂, odors, visible mold, complaints

IAQ monitor readings, filter status, occupant feedback

Energy

SEER2 ≥ 14.3, IEER ≥ 14.8, EUI < 50–80 kBtu/ft²/yr

High bills, short cycling, old equipment

Utility bills, equipment specs, run times

Noise

NC/RC 25–35 (offices/classrooms)

Complaints, hums, rattles, high dBA

Sound level readings, vibration checks

Code Compliance

2018 KY Building/Residential Code, permits, ACCA Manual S/J

Unlicensed work, missing permits, improper sizing

Permits, load calcs, inspection reports

Maintenance

$0.44–$0.61/ft²/yr, MTBF high, MTTR low

Frequent repairs, high costs, downtime

Maintenance logs, cost records, PM schedules

Tax/Incentives

30% federal credit, KY rebates

Missed opportunities, ineligible equipment

Receipts, certifications, rebate forms

Conclusion and Action Plan


A comprehensive evaluation of your company’s HVAC system requires a multi-faceted approach, integrating technical performance, regulatory compliance, financial analysis, and occupant well-being. By systematically assessing IAQ, energy consumption, noise, code compliance, maintenance costs, and available incentives, facility managers and business owners can make informed, data-driven decisions about whether to repair, upgrade, or replace their HVAC systems.


Action Steps:

  1. Conduct a Baseline Assessment: Use the provided checklists and measurement tools to document current system performance.

  2. Benchmark and Analyze: Compare findings to industry standards and peer facilities.

  3. Engage Qualified Professionals: For complex diagnostics, code compliance, or major upgrades, consult licensed HVAC contractors and energy auditors.

  4. Leverage Incentives: Monitor federal, state, and utility programs to maximize financial benefits.

  5. Implement Improvements: Prioritize actions based on risk, payback, and business needs.

  6. Monitor and Reassess: Establish ongoing monitoring and preventive maintenance to sustain performance and compliance.


By following this structured framework, Kentucky businesses can ensure their HVAC systems deliver optimal comfort, efficiency, and value—now and into the future.

Get in Touch

Lexington Office

680 Bizzell Dr. 

Lexington, KY 40510

859.255.9665

Louisville Office

13151 Middletown Industrial Blvd

Louisville, KY 40223

502.473.0829

Paducah Office

115 Eaglet Cove

Paducah, KY 42003

​270.898.6976

  • Facebook
  • LinkedIn
  • Instagram

Thanks for submitting!

bottom of page